| Code No | SL-125 | SL-163 | SL-1100 | SL-1200 | SL-1300 | SL-325 | SL-363 | SL-3100 | SL-3200 | SL-3300 | 
|---|---|---|---|---|---|---|---|---|---|---|
| Bushing Type (LV) | 1/250 | 1/630 | ML-1000 | 1/2000 | 1/3150 | 3/250 | 3/630 | 3/1000 | 3/2000 | 3/3150 | 
| Specification (DIN) | 42530 | 42530 | 42530 | 42530 | 42530 | 42539 | 42539 | 42539 | 42539 | 42539 | 
| Rated Current (A) | 250 | 630 | 1000 | 2000 | 3150 | 250 | 630 | 1000 | 2000 | 3150 | 
| Nominal Voltage (kV) | 1 | 1 | 1 | 1 | 1 | 3 | 3 | 3 | 3 | 3 | 
| Dry Lightning Impulse Voltage | - | - | - | - | - | 40 | 40 | 40 | 40 | 40 | 
| Wet power frequency Volt (kV) | - | - | - | - | - | 10 | 10 | 10 | 10 | 10 | 
| Dry power frequency Volt (kV) | - | - | - | - | - | 14 | 14 | 14 | 14 | 14 | 
| Creepage Distance (mm) | 60 | 75 | 75 | 75 | 75 | 120 | 120 | 125 | 125 | 125 | 
| Arching Distance (mm) | 50 | 60 | 60 | 60 | 60 | 100 | 100 | 100 | 100 | 100 | 
| Electrical Properties Of LV Bushings | ||||||||
|---|---|---|---|---|---|---|---|---|
| Type | Norm | Nominal Voltage (kV) | Rated Current (A) | Dry Lightening Impulse Voltage (kV) | Wet Power Frequency Voltage (kV) | Dry Power Frequency Voltage (kV) | Creepage Distance (mm) | Total Weight (kg) | 
| 1/250 | DIN 42530 | 1 | 250 | - | - | - | 55 | 0.7 | 
| 1/630 | DIN 42530 | 1 | 630 | - | - | - | 70 | 2 | 
| 1/1000 | DIN 42530 | 1 | 1000 | - | - | - | 75 | 3.9 | 
| 1/2000 | DIN 42530 | 1 | 2000 | - | - | - | 75 | 10.4 | 
| 1/3150 | DIN 42530 | 1 | 3150 | - | - | - | 75 | 13.9 | 
| 3/250 | DIN 42539 | 3 | 250 | 40 | 10 | 14 | 120 | 1 | 
| 3/630 | DIN 42539 | 3 | 630 | 40 | 10 | 14 | 120 | 2.5 | 
| 3/1000 | DIN 42539 | 3 | 1000 | 40 | 10 | 14 | 125 | 6 | 
| 3/2000 | DIN 42539 | 3 | 2000 | 40 | 10 | 14 | 125 | 13 | 
| 3/3150 | DIN 42539 | 3 | 3150 | 40 | 10 | 14 | 125 | 18 | 
| Mechanical Properties Of HV Bushings | ||||||||
|---|---|---|---|---|---|---|---|---|
| Type | Specification (DIN) | Operation Bending Load ACC. To IEC 137 (N) | Tightening Torque(Nm) | |||||
| DT 250 | DIN 42530 | 600 | 20 | |||||
| DT 630 | DIN 42530 | 1200 | 35 | |||||
| DT 1000 | DIN 42530 | 1500 | 70 | |||||
| DT 2000 | DIN 42530 | 2200 | 100 | |||||
| DT 3150 | DIN 42530 | 2400 | 200 | |||||